DiagCode State Name State Description and Output Setting
C006 Error timer
MaxMuting
Timing error: Active muting time (when S_MutingActive = TRUE) exceeds
MaxMutingTime.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
C007 Error timer
Entry
Timing error: Discrepancy time for switching S_MutingSwitch11 and
S_MutingSwitch12 from FALSE to TRUE > DiscTimeEntry.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Table 74: FB-specific status codes (no error):
DiagCode State Name State Description and Output Setting
0000 Idle The function block is not active (initial state).
Ready = FALSE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
8000 AOPD Free Muting not active and no safety demand from AOPD. If timers from subse-
quent muting are still running, they are stopped.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
8001 Init Function block was activated.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
8002 Safety
Demand
AOPD
Safety demand detected by AOPD, muting not active.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017 AC500-S 365