DiagCode State Name State Description and Output Setting
8003 Wait for Reset Safety demand or errors have been detected and are now cleared. Oper-
ator acknowledgment by Reset required.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
8005 Safe Safety function activated.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
8011 Muting Start 1 Muting sequence is in starting phase after rising trigger of S_MutingS-
witch11. Monitoring of DiscTimeEntry is activated.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
8311 Muting Start 2 Muting sequence is in starting phase after rising trigger of S_MutingS-
witch12. Monitoring of DiscTimeEntry is activated.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
8012 Muting Active Muting sequence is active either:
- After rising trigger of the second S_MutingSwitch 12 or 11 has been
detected.
- When both S_MutingSwitch 11 and 12 have been actuated in the same
cycle.
Monitoring of DiscTimeEntry is stopped. Monitoring of MaxMutingTime is
activated.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017AC500-S366