Table 81: FB Name: SF_OutControl
Name Data Type Initial Value Description, Parameter Values
VAR_INPUT
Activate BOOL FALSE
Ä
Table 31 “General Input Parameters”
on page 266
S_SafeControl BOOL FALSE Variable.
Control signal of the preceding safety FB.
Typical function block signals from the library
(e.g., SF_EStop, SF_GuardMonitoring, SF_Two-
HandControlTypeII, and/or others).
FALSE: The preceding safety FB’s are in safe
state.
TRUE: The preceding safety FB’s enable safety
control.
ProcessControl BOOL FALSE Variable or constant.
Control signal from the functional application.
FALSE: Request to set S_OutControl to FALSE.
TRUE: Request to set S_OutControl to TRUE.
StaticControl BOOL FALSE Constant.
Optional conditions for process control.
FALSE: Dynamic change at ProcessControl
(FALSE => TRUE) required after block activation
or triggered safety function. Additional function
start required.
TRUE: No dynamic change at ProcessControl
(FALSE => TRUE) required after block activation
or triggered safety function.
S_StartReset BOOL FALSE
Ä
Table 31 “General Input Parameters”
on page 266
S_AutoReset BOOL FALSE
Ä
Table 31 “General Input Parameters”
on page 266
Reset BOOL FALSE
Ä
Table 31 “General Input Parameters”
on page 266
VAR_OUTPUT
Ready BOOL FALSE
Ä
Table 32 “General Output Parameters”
on page 267
S_OutControl BOOL FALSE Controls connected actuators.
FALSE: Disable connected actuators.
TRUE: Enable connected actuators.
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017 AC500-S 381