Table 86: FB-specific status codes (no error):
DiagCode State Name State Description and Output Setting
0000 Idle The function block is not active (initial state).
Ready = FALSE
S_EDM_Out = FALSE
Error = FALSE
8001 Init Block activation startup inhibit is active. Reset required.
Ready = TRUE
S_EDM_Out = FALSE
Error = FALSE
8010 Output Disable EDM control is not active. Timer starts when state is entered.
Ready = TRUE
S_EDM_Out = FALSE
Error = FALSE
8000 Output Enable EDM control is active. Timer starts when state is entered.
Ready = TRUE
S_EDM_Out = TRUE
Error = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017AC500-S394