3. Verify against your safety application technical specification that all iParameters for all Safety I/O chan-
nels are set correctly.
4. Go to F-Parameter tab and press “Calculate” button. Copy calculated F_iPar_CRC value from the
“Checksum iParameter” field and paste it to F_iPar_CRC field of the F-Parameter editor (see below).
Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification procedure workflow