F_iPar_CRC value is safely saved now.
5. Go to “DX581-S Configuration”, “DI581-S Configuration” or “AI581-S Configuration” tabs, respectively,
and verify using a cross-check according
Ä
Chapter 6.5.2 “ Verification tables for iParameter settings
in AC500-S Safety I/Os” on page 417 that iParameter settings previously set at Step 2 are the same as
ones listed in the “Value” column for given channels (use
Ä
Chapter 6.5.2 “ Verification tables for
iParameter settings in AC500-S Safety I/Os” on page 417 to decode integer values to real parameter
values).
Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification procedure workflow