EasyManua.ls Logo

ABB AC500-S - 6.5.2.1 AI581-S Safety I;O tables

ABB AC500-S
452 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.5.2.1 AI581-S Safety I/O tables
Fig. 128: The “AI581-S Configuration” Tab is a readback view for iParameters set in “AI581-S” Tab.
1 “AI581-S” Tab
2 “AI581-S Configuration” Tab
1. Compare that “Check supply” parameters have the same values “On” or “Off” (English settings) in both
“AI581-S” and “AI581-S Configuration” tabs.
2. Refer to “AI581-S” tab and calculate “Input channel 0” decimal equivalent (Dec_InputChannel0) as:
Dec_InputChannel0 = Configuration_Value + Noise_Rejection_Value
where:
Configuration_Value:
0 Not used
3 1 channel (0 … 20 mA)
4 1 channel (4 … 20 mA)
5 2 channel (4 … 20 mA)
Noise_Rejection_Value:
0 None
64 50 Hz
128 60 Hz
Compare calculated Dec_InputChannel0 (
Ä
step 2) with “Input 0, channel configuration value”.
They have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
3. Repeat step 2 for the rest of analog input channels (Input 1, Input 2 and Input 3).
4. Refer to “AI581-S” tab and calculate “Analog inputs 0/2 – Extended configuration” decimal equiva-
lent (Dec_ExtConf0_2) as:
Dec_ExtConf0_2 = Tolerance_Range_Value + Min_Max_Value
where
Tolerance_Range_Value:
4 4 %
Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
Safety I/Os
30.03.2017AC500-S418

Table of Contents

Other manuals for ABB AC500-S

Related product manuals