5 5 %
6 6 %
7 7 %
8 8 %
9 9 %
10 10 %
11 11 %
12 12 %
Min_Max_Value:
0 Min
128 Max
Compare calculated Dec_ExtConf0_2 (
Ä
Step 5) with “Analog inputs 0/2 – Extended configura-
tion”. They have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
5. Repeat step 4 for “Analog inputs 1/3 – Extended configuration” value.
Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
Safety I/Os
30.03.2017 AC500-S 419