64 On
Output_Value:
0 Not used
128 Used
Compare calculated Dec_OutputChannel0 (
Ä
step 7) with “Output 0, channel configuration”. They
have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
7. Repeat step 6 for the rest of digital output channels (Channel 1, Channel 2, … Channel 7).
Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
Safety I/Os
30.03.2017AC500-S424