EasyManua.ls Logo

ABB AC500-S - Page 423

ABB AC500-S
452 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
96 30 ms
112 50 ms
128 100 ms
144 200 ms
160 500 ms
Compare calculated Dec_InputChannel0 (
Ä
step 2) with “Input 0, channel configuration value”.
They have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
3. Repeat step 2 for the rest of digital input channels (Input 1, Input 2, … Input 7).
4. Compare that “2 channel configuration 0/4” parameter in “DX581-S” tab have the same value as
“Inputs 0/4, discrepancy time” parameter in “DX581-S Configuration” tab.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
Fig. 132: Compare “DX581-S” tab and “DX581-S Configuration” tab
1 2 channel configuration 0/4” parameter in
“DX581-S” tab
2 “Inputs 0/4, discrepancy time” parameter in
“DX581-S Configuration” tab
5. Repeat Step 4 for the rest of input channel combinations:
n Inputs 1/5, discrepancy time
n Inputs 2/6, discrepancy time
n Inputs 3/7, discrepancy time
6. Refer to “DX581-S” tab and calculate “Output channel 0” decimal equivalent (Dec_OutputChannel0)
as:
Dec_OutputChannel0 = Detection_Value + Output_Value + 1
where
Detection_Value:
0 Off
Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
Safety I/Os
30.03.2017 AC500-S 423

Table of Contents

Other manuals for ABB AC500-S

Related product manuals