6.5.2.3 DX581-S Safety I/O tables
Fig. 131: The “DX581-S Configuration” Tab is a readback view for iParameters set in “DX581-S” Tab.
1 “DX581-S” Tab
2 “DX581-S Configuration” Tab
1. Compare that “Check supply” parameters have the same values “On” or “Off” (English settings) in both
“DX581-S” and “DX581-S Configuration” tabs.
2. Refer to “DX581-S” tab and calculate “Input channel 0” decimal equivalent (Dec_InputChannel0) as:
Dec_InputChannel0 = Configuration_Value + Test_Pulse_Value + Input_Delay_Value
where
Configuration_Value:
0 Not used
1 1 channel
2 2 channel equivalent
3 2 channel antivalent
Test_Pulse_Value:
0 Disabled
8 Enabled
Input_Delay_Value:
16 1 ms
32 2 ms
48 5 ms
64 10 ms
80 15 ms
Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
Safety I/Os