128 ➔ 100 ms
144 ➔ 200 ms
160 ➔ 500 ms
Compare calculated Dec_InputChannel0 (
Ä
step 2) with “Input 0, channel configuration value”.
They have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
3. Repeat step 2 for the rest of digital input channels (Input 1, Input 2, … Input 15).
4. Compare that “2 channel configuration 0/8” parameter in “DI581-S” tab have the same value as “Inputs
0/8, discrepancy time” parameter in “DI581-S Configuration” tab.
The values have to be the same.
If they are not the same, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
Fig. 130: Compare “DI581-S” tab and “DI581-S Configuration” tab
1 “2 channel configuration 0/8” parameter in
“DI581-S” tab
2 “Inputs 0/8, discrepancy time” parameter in
“DI581-S Configuration” tab
5. Repeat step 4 for the rest of channel combinations:
n Inputs 1/9, discrepancy time
n Inputs 2/10, discrepancy time
n Inputs 3/11, discrepancy time
n Inputs 4/12, discrepancy time
n Inputs 5/13, discrepancy time
n Inputs 6/14, discrepancy time
n Inputs 7/15, discrepancy time
Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
Safety I/Os
30.03.2017 AC500-S 421