Appendix A – ACS/ACC/ACP 601 Technical Data
A-10 ACx=ACS/ACC/ACP ACS/ACC/ACP 601 Drives
Cooling Air Flow
Requirements
Cooling air flow requirements are given below.
Cooling Air Duct
Heat dissipations and cooling air flows of ACx 601 in a cooling air duct
installation are below.
ACx 601
Flow
m
3
/h
Flow
ft
3
/h
ACx 601-0005-3/0006-5 40 25
ACx 601-0006-3/0009-5 40 25
ACx 601-0009-3/0011-5 40 25
ACx 601-0011-3/0016-5/0009-6/0011-6 60 35
ACx 601-0016-3/0020-5/0016-6/0020-6 60 35
ACx 601-0020-3/0025-5/0025-6 70 40
ACx 601-0025-3/0030-5/0030-6 100 60
ACx 601-0030-3/0040-5/0040-6 260 155
ACx 601-0040-3/0050-5/0050-6 260 155
ACx 601-0050-3/0060-5 260 155
ACx 601-0060-3/0070-5/0060-6 280 165
ACx 601-0070-3/0100-5/0070-6 280 165
ACx 601-0100-3/0120-5/0100-6 660 390
ACx 601-0120-3/0140-5/0120-6 660 390
Degree of
protection
Heat Dissipation Degree of
protection
Cooling Air Flow Out
Heatsink Front Section Heatsink Front Section
IP 22 85 % of
ACx 600 losses
15 % of
ACx 600 losses
IP 22 80 % of air flow 20 % of air flow
IP 54 90 % of
ACx 600 losses
10 % of
ACx 600 losses
IP 54 100 % of air flow 0 % of air flow