Appendix A – ACS/ACC/ACP 601 Technical Data
A-4 ACx=ACS/ACC/ACP ACS/ACC/ACP 601 Drives
Example 2.
If the ambient temperature is 122 °F, the output current
for ACx 601-0006-3 is first calculated at 104 °F (derating factor 92
% or 0.92 from Curve 2) and the result is multiplied by factor 0.65
(See
Example 1
(IP 21/22)). The output current is then 0.92 · 0.65 ·
I
2N
or 0.92 · 0.65 ·
I
2hd
.
Output Current Ratings
for IP54 Enclosures
Output current for ACS/ACC/ACP 601 with degree of protection IP 54
and with ambient temperature from 25 °C to 40 °C is presented in the
diagram below.
I
2N
total rms output current for normal use,
I
2hd
total
rms output current for heavy-duty use,
t
ambient temperature.
Fuses
Recommended input fuse ratings of the ACS/ACC/ACP 601 are below.
A minimum rated current in amperes, A
2
s maximum I
2
t value, V rated
voltage in volts. Only ultra rapid fuses guarantee proper protection for
the rectifier semiconductors.
24 26 28 30 32 34 36 38 40
77 86 95 104
100
95
90
85
80
75
70
65
60
Curve 1
(100 %
no derating)
Curve 2 Curve 3 Curve 4 Curve 5
ACx 601-0005-3 ACx 601-0006-3 ACx 601-0011-3 ACx 601-0009-3 ACx 601-0016-3
ACx 601-0006-5 ACx 601-0009-5 ACx 601-0020-3 ACx 601-0040-3 ACx 601-0070-3
ACx 601-0009-6 ACx 601-0025-5 ACx 601-0025-3 ACx 601-0050-3 ACx 601-0020-5
ACx 601-0011-6 ACx 601-0070-5 ACx 601-0030-3 ACx 601-0011-5 ACx 601-0100-5
ACx 601-0100-6 ACx 601-0016-6 ACx 601-0060-3 ACx 601-0050-5 ACx 601-0070-6
ACx 601-0120-6 ACx 601-0016-5 ACx 601-0060-5
ACx 601-0030-5 ACx 601-0040-6
ACx 601-0040-5 ACx 601-0050-6
ACx 601-0020-6
ACx 601-0025-6
ACx 601-0030-6
ACx 601-0060-6
% of
I
2N
and
I
2hd
2
3
4
5
1
°C
°F