09 OPERATION
3BHS213401 E01 REV H ACS1000 AIR-COOLED USER MANUAL 122/184
- If a fault cannot be reset, it must be rectified by the responsible personnel.
- When no alarms and faults are present and the drive is ready, the CDP control panel
displays RdyForMCBOn:
3. Press the MAIN SUPPLY ON pushbutton on the control compartment door to close the MCB
and charge the DC link.
- The pushbutton lights up.
- The status line of the CDP control panel changes to Charging.
After charging has been finished, the following takes place:
- The protection IGCTs are closed.
- The status line of the CDP control panel changes to Rdy to Strt and the motor can
be started.
4. Enter the reference value.
LOC RESET REF
REM
1 L -> 0.0 rpm
Status RdyForMCBon
MotorSpeed 0.00 rpm
Power 0.0 %
1 L -> 0.0 rpm
Status Charging
MotorSpeed 0.00 rpm
Power 0.0 %
1 L -> 0.0 rpm 0
Status Ready to Strt
MotorSpeed 0.00 rpm
Power 0.0 %