09 OPERATION
3BHS213401 E01 REV H ACS1000 AIR-COOLED USER MANUAL 124/184
9.8 Stopping the drive
1. Press the STOP key on the CDP control panel.
- The motor stops according to the preset stop function and the drive stops modulating.
While the motor stops, the status line of the display shows Stopping. The run status
message blinks during the stop sequence.
- As long as the stop sequence is in progress, the drive can always be restarted by
pressing the START key on the CDP control panel.
- When the drive has stopped modulating, the CDP control panel displays Rdy to Strt.
Note: As long as the MCB has not been opened, the motor can be started again.
I0
1 L -> 600.0 rpm I
Status Stopping
MotorSpeed 300.0 rpm
Power 20.0 %
LOC RESET REF
REM
1 L -> 600.0 rpm 0
Status Rdy to Strt
MotorSpeed 0.0 rpm
Power 0.0 %