Parameters 129
14.09 DIO2 Toff Defines the off (deactivation) delay for digital input/output
DIO2 when 14.06 DIO2 conf is set to Output. See parameter
14.08 DIO2 Ton.
0.0 … 3000.0 s Off (deactivation) delay for DIO2 when set as an output. 10 = 1 s
14.10 DIO3 conf Selects whether DIO3 is used as a digital output, digital input
or frequency output.
Output DIO3 is used as a digital output. 0
Input DIO3 is used as a digital input. 1
Freq output DIO3 is used as a frequency output. 3
14.11 DIO3 out src Selects a drive signal to be connected to digital output DIO3
(when 14.10 DIO3 conf is set to Output).
Brake cmd 03.16 Brake command (see page 101). 1073742608
Ready Bit 0 of 06.01 Status word1 (see page 103). 1073743361
Enabled Bit 1 of 06.01 Status word1 (see page 103). 1073808897
Started Bit 2 of 06.01 Status word1 (see page 103). 1073874433
Running Bit 3 of 06.01 Status word1 (see page 103). 1073939969
Alarm Bit 7 of 06.01 Status word1 (see page 103). 1074202113
Ext2 active Bit 8 of 06.01 Status word1 (see page 103). 1074267649
Fault Bit 10 of 06.01 Status word1 (see page 103). 1074398721
Fault(-1) Bit 12 of 06.01 Status word1 (see page 103). 1074529793
Ready relay Bit 2 of 06.02 Status word2 (see page 104). 1073874434
RunningRelay Bit 3 of 06.02 Status word2 (see page
104). 1073939970
Ref running Bit 4 of 06.02 Status word2 (see page 104). 1074005506
Charge ready Bit 9 of 06.02 Status word2 (see page 104). 1074333186
Neg speed Bit 0 of 06.03 Speed ctrl stat (see page 105). 1073743363
Zero speed Bit 1 of 06.03 Speed ctrl stat (see page 105). 1073808899
Above limit Bit 2 of 06.03 Speed ctrl stat (see page 105). 1073874435
At setpoint Bit 3 of 06.03 Speed ctrl stat (see page 105). 1073939971
Supervision1 Bit 0 of 06.13 Superv status (see page 106). 1073743373
Supervision2 Bit 1 of 06.13 Superv status (see page 106). 1073808909
Supervision3 Bit 2 of 06.13 Superv status (see page 106). 1073874445
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
14.14 DIO4 conf Selects whether DIO4 is used as a digital output or input.
Output DIO4 is used as a digital output. 0
Input DIO4 is used as a digital input. 1
14.15 DIO4 out src Selects a drive signal to be connected to digital output DIO4
(when 14.14 DIO4 conf is set to Output).
Brake cmd 03.16 Brake command (see page 101). 1073742608
Ready Bit 0 of 06.01 Status word1 (see page 103). 1073743361
Enabled Bit 1 of 06.01 Status word1 (see page
103). 1073808897
Started Bit 2 of 06.01 Status word1 (see page 103). 1073874433
Running Bit 3 of 06.01 Status word1 (see page 103). 1073939969
No. Name/Value Description FbEq