Parameters 135
14.43 RO1 Ton Defines the on (activation) delay for relay output RO1.
0.0 … 3000.0 s On (activation) delay for RO1. 10 = 1 s
14.44 RO1 Toff Defines the off (deactivation) delay for relay output RO1. See
parameter 14.43 RO1 Ton.
0.0 … 3000.0 s Off (deactivation) delay for RO1. 10 = 1 s
14.45 RO2 src Selects a drive signal to be connected to relay output RO2.
Brake cmd 03.16 Brake command (see page 101). 1073742608
Ready Bit 0 of 06.01 Status word1 (see page 103). 1073743361
Enabled Bit 1 of 06.01 Status word1 (see page 103). 1073808897
Started Bit 2 of 06.01 Status word1 (see page 103). 1073874433
Running Bit 3 of 06.01 Status word1 (see page 103). 1073939969
Alarm Bit 7 of 06.01 Status word1 (see page 103). 1074202113
Ext2 active Bit 8 of 06.01 Status word1 (see page 103). 1074267649
Fault Bit 10 of 06.01 Status word1 (see page 103). 1074398721
Fault(-1) Bit 12 of 06.01 Status word1 (see page 103). 1074529793
Ready relay Bit 2 of 06.02 Status word2 (see page 104). 1073874434
RunningRelay Bit 3 of 06.02 Status word2 (see page 104). 1073939970
Ref running Bit 4 of 06.02 Status word2 (see page 104). 1074005506
Charge ready Bit 9 of 06.02 Status word2 (see page 104). 1074333186
Neg speed Bit 0 of 06.03 Speed ctrl stat (see page 105). 1073743363
Zero speed Bit 1 of 06.03 Speed ctrl stat (see page 105). 1073808899
Above limit Bit 2 of 06.03 Speed ctrl stat (see page 105). 1073874435
At setpoint Bit 3 of 06.03 Speed ctrl stat (see page 105). 1073939971
Supervision1 Bit 0 of 06.13 Superv status (see page 106). 1073743373
Supervision2 Bit 1 of 06.13 Superv status (see page 106). 1073808909
Supervision3 Bit 2 of 06.13 Superv status (see page 106). 1073874445
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
No. Name/Value Description FbEq
1
0
1
0
t
On
t
Off
t
On
t
Off
t
On
14.43 RO1 Ton
t
Off
14.44 RO1 Toff
Drive status
RO1 status
Time