Parameters 215
Raw data No scaling (i.e. data is transmitted without scaling). Source
for the actual value, which is sent to the fieldbus, is selected
by parameter 50.06 Fba act1 tr src.
0
Torque Fieldbus adapter module uses torque reference scaling.
Torque reference scaling is defined by the used fieldbus
profile (e.g. with ABB Drives Profile integer value 10000
corresponds to 100% torque value). Signal 01.06 Motor
torque is sent to the fieldbus as an actual value. See the
User’s Manual of the appropriate fieldbus adapter module.
1
Speed Fieldbus adapter module uses speed reference scaling.
Speed reference scaling is defined by the used fieldbus
profile (e.g. with ABB Drives Profile integer value 20000
corresponds to parameter 19.01 Speed scaling value). Signal
01.01 Motor speed rpm is sent to the fieldbus as an actual
value. See the User’s Manual of the appropriate fieldbus
adapter module.
2
50.05 Fba ref2 modesel Selects the fieldbus reference FBA REF2 scaling.
See parameter 50.04 Fba ref1 modesel.
Raw data See parameter 50.04 Fba ref1 modesel.0
Torque See parameter 50.04 Fba ref1 modesel.1
Speed See parameter 50.04 Fba ref1 modesel.2
50.06 Fba act1 tr src Selects the source for fieldbus actual value 1 when parameter
50.04 Fba ref1 modesel / 50.05 Fba ref2 modesel is set to
Raw data.
Pointer Value pointer setting (see Terms and abbreviations on page
93).
-
50.07 Fba act2 tr src Selects the source for fieldbus actual value 2 when parameter
50.04 Fba ref1 modesel / 50.05 Fba ref2 modesel is set to
Raw data.
Pointer Value pointer setting (see Terms and abbreviations on page
93).
-
50.08 Fba sw b12 src Selects the source for freely programmable fieldbus status
word bit 28 (02.24 FBA main sw bit 28 SW B28).
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
50.09 Fba sw b13 src Selects the source for freely programmable fieldbus status
word bit 29 (02.24 FBA main sw bit 29 SW B29).
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
50.10 Fba sw b14 src Selects the source for freely programmable fieldbus status
word bit 30 (02.24 FBA main sw bit 30 SW B30).
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
50.11 Fba sw b15 src Selects the source for freely programmable fieldbus status
word bit 31 (02.24 FBA main sw bit 31 SW B31).
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
No. Name/Value Description FbEq