Startup Assistant & Parameters 12-273AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
CONTROL AND
STATUS WORDS
(Continued)
MAIN CONTROL WORD
(06.01) (Cont.)
Default: Read Only
Range: 0 - 15
10 (Remote cmd)
1 - Fieldbus control enabled.
0 - Control word and reference not getting through to the drive, except
for bits 0…2.
11 (Ext ctrl loc)
1 - Select External Control Location EXT2. Effective if control location
is parameterized to be selected from eldbus.
0 - Select External Control Location EXT1. Effective if control location
is parameterized to be selected from eldbus.
12 - 15 (Reserved)
The main control word of the drive. This parameter shows the control
signals as received from the selected sources (such as digital inputs,
the eldbus interfaces and the application program).
Note: Bits 12 - 15 can be used to carry additional control data, and used
as a signal source by any binary-source selector parameter.
APPLICATION CONTROL
WORD (06.02)
Default: Read Only
Range: 0000h - FFFFh
Application program control word. The drive control word received
from the application program (if any).
This parameter is read-only.
FBA A TRANSPARENT
CONTROL WORD (06.03)
Default: Read Only
Range: 00000000h - FFFFFFFFh
Control word received through eldbus adapter A. Displays the
unaltered control word received from the PLC through eldbus
adapter A when a transparent communication prole is selected eg.
by parameter group 51 FBA A settings. See section Control word and
Status word.
This parameter is read-only.
FBA B TRANSPARENT
CONTROL WORD (06.04)
Default: Read Only
Range: 00000000h - FFFFFFFFh
Control word received through eldbus adapter B. Displays the
unaltered control word received from the PLC through eldbus
adapter B when a transparent communication prole is selected eg.
by parameter group 54 FBA B settings. See section Control word and
Status word.
This parameter is read-only.
EFB TRANSPARENT
CONTROL WORD (06.05)
Default: Read Only
Range: 00000000h - FFFFFFFFh
Control word received through the embedded eldbus interface.
Displays the unaltered control word received from the PLC through
the embedded eldbus interface when a transparent communication
prole is selected in parameter 58.25 Control prole. See section The
Transparent prole.
This parameter is read-only.