12-28 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
CONTROL AND
STATUS WORDS
(Continued)
MAIN STATUS WORD (06.11) Default: Read Only
Range: 0 - 15
Main status word of the drive. This parameter is read-only.
Bit Name Value Description
0
Ready to
switch ON
1 Ready to switch ON
0 Not ready to switch ON
1 Ready run
1 Ready to operate
0
OFF1 active
2 Ready ref
1
Operation enabled
0
Operation inhibited
3 Tripped
1
Fault
0
No Fault
4 OFF2 inactive
1
OFF2 inactive
0
OFF2 active
5 OFF3 inactive
1
OFF3 inactive
0
OFF3 active
6
Switch-on
inhibited
1
Switch-on inhibited
0
--
7 Warning
1
Warning active
0
No warning active
8
At setpoint
1
Operating - Actual value equals
reference = is within
tolerance limits (see parameters
46.21 - 46.23)
0
Actual value differs from reference
= is outside tolerance
limits
9
Remote
1
Drive control location: Remote
(EXT1 or EXT2)
0
Drive control location: Local
10
Trickle Current
Active
0
Trickle Current OFF
1 Trickle Current ON
11
De-Ice Mode
Active
0 De-Ice Mode OFF
1 De-Ice Mode ON
12
CTD Run
0 CTD Drive Not Running
1 CTD Drive Running
13
CTD HOLD
0 CTD Autophase OFF
1 CTD Autophase ON
14
User bit 3
- See parameter 06.33 MSW bit 14
sel
15
Reserved