Startup Assistant & Parameters 12-293AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
CONTROL AND
STATUS WORDS
(Continued)
DRIVE STATUS WORD 1
(06.16)
Default: Read Only
Range: 0000h - FFFFh
Drive status word 1. This parameter is read-only.
Bit Name
Descriptions
0
Enabled
1 = Both run enable (see par. 20.12) and
start enable (20.19)
signals are present
Note: This bit is not affected by the
presence of a fault
1
Inhibited
1 = Start inhibited - See parameters 06.18
and 06.25 for the
source of the inhibiting signal
2
DC charged 1 = DC circuit has been charged
3
Ready to
start
1 = Drive is ready to receive a start
command
4
Following
reference
1 = Drive is ready to follow given reference
5
Started 1 = Drive has been started
6
Modulating
1 = Drive is modulating (output stage is
being controlled)
7
Limiting
1 = Any operating limit (speed, torque,
etc.) is active
8
Local control 1 = Drive is in local control
Network ctrl 1 = Drive is in network control
10
Ext1 active 1 = Control location Ext1 active
11
Ext2 active 1 = Control location Ext2 active
12
Reserved
13
Start request 1 = Start requested
14-15
Reserved