Startup Assistant & Parameters 12-313AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
CONTROL AND
STATUS WORDS
(Continued)
START INHIBIT STATUS
WORD (06.18)
Default: Read Only
Range: 0000h - FFFFh
Start inhibit status word. This word species the source of the
inhibiting signal that is preventing the drive from starting. The
conditions marked with an asterisk (*) only require that the start
command is cycled. In all other instances, the inhibiting condition
must be removed rst.
See also parameter 06.25 Drive inhibit status word 2, and 06.16 Drive
status word 1, bit 1. This parameter is read-only.
Bit Name
Descriptions
0
Not ready run
1 = DC voltage is missing or drive has not
been parametrized
correctly - Check the parameters in groups
95 and 99
1
Ctrl location
changed
* 1 = Control location has changed
2
SSW inhibit
1 = Control program is keeping itself in
inhibited state
3
Fault reset * 1 = A fault has been reset
4
Lost start enable 1 = Start enable signal missing
5
Lost run enable 1 = Run enable signal missing
6
FSO inhibit
1 = Operation prevented by FSO-xx safety
functions module
7
STO 1 = Safe torque off active
8
Current
Calibration ended
* 1 = Current calibration routine has nished
9
ID run ended * 1 = Motor identication run has nished
10
Auto phase
ended
* 1 = Autophasing routine has nished
11
Em Off1 1 = Emergency stop signal (mode Off1)
12
Em Off2 1 = Emergency stop signal (mode Off2)
13
Em Off3 1 = Emergency stop signal (mode Off3)
14
Auto reset inhibit
1 = The autoreset function is inhibiting
operation
15
Jogging active
1 = The jogging enable signal is inhibiting
operation