Startup Assistant & Parameters 12-313AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
CONTROL AND
STATUS WORDS
(Continued)
START INHIBIT STATUS
WORD (06.18)
Default: Read Only
Range: 0000h - FFFFh
Start inhibit status word. This word species the source of the
inhibiting signal that is preventing the drive from starting. The
conditions marked with an asterisk (*) only require that the start
command is cycled. In all other instances, the inhibiting condition
must be removed rst.
See also parameter 06.25 Drive inhibit status word 2, and 06.16 Drive
status word 1, bit 1. This parameter is read-only.
Bit Name
Descriptions
0
Not ready run
1 = DC voltage is missing or drive has not
been parametrized
correctly - Check the parameters in groups
95 and 99
1
Ctrl location
changed
* 1 = Control location has changed
2
SSW inhibit
1 = Control program is keeping itself in
inhibited state
3
Fault reset * 1 = A fault has been reset
4
Lost start enable 1 = Start enable signal missing
5
Lost run enable 1 = Run enable signal missing
6
FSO inhibit
1 = Operation prevented by FSO-xx safety
functions module
7
STO 1 = Safe torque off active
8
Current
Calibration ended
* 1 = Current calibration routine has nished
9
ID run ended * 1 = Motor identication run has nished
10
Auto phase
ended
* 1 = Autophasing routine has nished
11
Em Off1 1 = Emergency stop signal (mode Off1)
12
Em Off2 1 = Emergency stop signal (mode Off2)
13
Em Off3 1 = Emergency stop signal (mode Off3)
14
Auto reset inhibit
1 = The autoreset function is inhibiting
operation
15
Jogging active
1 = The jogging enable signal is inhibiting
operation