12-90 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
SYSTEM
(Continued)
ACCESS LEVELS STATUS
(96.03)
Default: Read Only
Range: -
11 Expert Commissioner
12 Fieldbus
13 CTDD User
Shows which access levels have been activated by pass codes entered
into parameter 96.02 Pass code.
Parameter 96.03 shows the current access level setting, note ABB default
will show active with the addition of the set level shown above. Value is
offset by one from the password entered.
MACRO SELECT (96.04) Default: CTDD
Range:
CTDD
Done
Selects the application macro. Only CTDD macro is available.
After a selection is made, the parameter reverts automatically to Done.
NOTE: Selecting 96.04 will cause a reset to factory default (selecting
CTDD).
MACRO ACTIVE (96.05) Default: Read Only
Range: CTDD
CTDD
Defaults to CTDD.
To change the macro, use parameter 96.04 Macro select.
PARAMETER RESTORE (96.06) Default: 0 (Done)
Range: 0, 8, 62
0 (Done)
Restoring is completed.
8 (Restore defaults)
All editable parameter values are restored to default values, except
• motor data and ID run results
• control panel/PC communication settings
• I/O extension module settings
• eldbus adapter settings
• encoder conguration data
• parameter 95.20 HW options word 1 and the differentiated defaults
implemented by it.
62 (Clear all)
All editable parameter values are restored to default values, except
• control panel/PC communication settings
• eldbus adapter settings
• parameter 95.20 HW options word 1 and the differentiated defaults
implemented by it.
PC tool communication is interrupted during the restoring.
Restores the original settings of the control program (parameter default
values).
Note: This parameter cannot be changed while the drive is running.