Startup Assistant & Parameters 12-913AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
SYSTEM
(Continued)
PARAMETER SAVE
MANUALLY (96.07)
Default: 0 (Done)
Range: 0, 1
0 (Done) Save completed.
1 (Save) Save in progress.
Saves the valid parameter values to permanent memory. This parameter
should be used to store values sent from a eldbus, or when using an
external power supply to the control board as the supply might have a
very short hold-up time when powered off.
Note: A new parameter value is saved automatically when changed from
the PC tool or control panel but not when altered through a eldbus
adapter connection.
UNIT SELECTION (96.16) Default: 0001 0001
Range: 0000h - FFFFh
Selects the unit of parameters indicating power, temperature and torque.
Default setting is HP, °F and lb-ft.
Bit Name Information
0 Power unit
0 = kW
1 = hp default
1 Reserved
2 Temperature unit
0 = C (°C) default
1 = F (°F)
3 Reserved
4 Torque unit
0 = Nm (N·m)
1 = lbft (lb·ft) default
5 - 15 Reserved