Troubleshooting 13-133AXD50000011888
Table 13-2 Fault Messages (Alphabetical by Keypad Text)
Fault Fault # Cause What to do
Measurement
circuit ADC
5691 Measurement circuit fault. Contact your local ABB representative.
PU board powerfail 5692 Power unit power supply
failure.
Contact your local ABB representative.
Measurement
circuit DFF
5693 Measurement circuit fault. Contact your local ABB representative.
PU communication
conguration
5694 Version check cannot nd
a matching power unit
FPGA logic.
Contact your local ABB representative.
Reduced run 5695 Number of inverter
modules detected does
not match the value of
parameter 95.13
Reduced run mode.
Check that the value of 95.13 Reduced run mode
corresponds to the number of inverter modules present.
Check that the modules present are powered from the
DC bus and connected by ber optic cables to the BCU
control unit.
If all modules of the inverter unit are in fact available
(eg. maintenance work has been completed), check
that parameter 95.13 is set to 0 (reduced run function
disabled).
PU state feedback 5696 State feedback from
output phases does not
match control signals.
Contact your local ABB representative.
Charging feedback 5697 Charging feedback signal
missing.
Check the feedback signal coming from the charging
system.
Unknown power
unit fault
5698 Unidentied power unit
logic fault.
Check power unit logic and rmware compatibility.
Contact your local ABB representative.
Internal SW error 6180 Internal error. Contact your local ABB representative.
Quote the auxiliary code (check the event details in the
event log).
FPGA version
incompatible
6181 Firmware and FPGA le
version in the power unit
are incompatible.
Reboot the control unit (using parameter 96.08 Control
board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
FBA A mapping le 6306 Fieldbus adapter A
mapping le read error.
Contact your local ABB representative.
FBA B mapping le 6307 Fieldbus adapter B
mapping le read error.
Contact your local ABB representative.
Task overload 6481 Internal fault. Reboot the control unit (using parameter 96.08 Control
board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
Stack overow 6487 Internal fault. Reboot the control unit (using parameter 96.08 Control
board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
Internal le load 64A1 File read error. Reboot the control unit (using parameter 96.08 Control
board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
Internal record load 64A2 Internal record load error. Contact your local ABB representative.
Application loading 64A3 Application le
incompatible or corrupted.
Reboot the control unit (using parameter 96.08 Control
board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
Memory unit
detached
64B0 The memory unit was
detached when the
control unit was powered.
Switch off the power to the control unit and reinstall
the memory unit. In case the memory unit was not
actually removed when the fault occurred, check that
the memory unit is properly inserted into its connector
and its mounting screw is tight. Reboot the control unit
(using parameter 96.08 Control board boot) or by cycling
power. If the problem persists, contact your local ABB
representative.