13-14 Troubleshooting 3AXD50000011888
Table 13-2 Fault Messages (Alphabetical by Keypad Text)
Fault Fault # Cause What to do
Internal SSW fault 64B1 Internal fault. Reboot the control unit (using parameter 96.08 Control
board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
User set fault 64B2 Loading of user parameter
set failed because
• requested set does
not exist
• set is not compatible
with control program
• drive was switched off
during loading.
Ensure that a valid user parameter set exists. Reload if
uncertain.
Kernel overload 64E1 Operating system error. Reboot the control unit (using parameter 96.08 Control
board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
Parameter system 6581 Parameter load or save
failed.
Try forcing a save using parameter 96.07 Parameter save
manually. Retry.
FBA A parameter
conict
65A1 The drive does not have a
functionality requested by
PLC, or requested
functionality has not been
activated.
Check PLC programming.
Check settings of parameter groups 50 Fieldbus adapter
(FBA) and 51 FBA A settings.
FBA B parameter
conict
65A2 The drive does not have a
functionality requested by
PLC, or requested
functionality has not been
activated.
Check PLC programming.
Check settings of parameter groups 50 Fieldbus adapter
(FBA) and 54 FBA B settings.
Text data overow 6881 Internal fault. Reset the fault. Contact your local ABB representative if
the fault persists.
Text 32-bit table
overow
6882 Internal fault. Reset the fault. Contact your local ABB representative if
the fault persists.
Text 64-bit table
overow
6883 Internal fault. Reset the fault. Contact your local ABB representative if
the fault persists.
Text le overow 6885 Internal fault. Reset the fault. Contact your local ABB representative if
the fault persists.
Option module
comm loss
7080 Communication between
drive and an option
module is lost.
Check that all option modules are properly seated in their
slots.
Check that all option modules or slot connectors are
not damaged. To pinpoint the problem, try installing the
modules into different slots one at a time.
Panel port
communication
Programmable fault: 49.05
Communication loss action
7081 Control panel or PC tool
selected as active control
location for drive has
ceased communicating.
Check PC tool or control panel connection.
Check control panel connector. Disconnect and reconnect
the control panel.
Ext I/O comm loss 7082 The I/O extension module
types specied by
parameters do not
match the detected
conguration.
Check the event log for an auxiliary code (format XXYY
YYYY). “XX” species the number of the I/O extension
module (01: parameter group 14 I/O extension module
1, 02: 15 I/O extension module 2, 03: 16 I/O extension
module 3). “YY YYYY” indicates the problem (see actions
for each code below).
00 0001 Communication with
module failed.
Check that the module is properly seated in its slot.
Check that the module and the slot connector is not
damaged. Try installing the module into another slot.
00 0002 Module not found. Check the type and location settings of the modules
(parameters 14.01/14.02, 15.01/15.02 or 16.01/16.02).
Check that the module is properly seated in its slot.
Check that the module and the slot connector is not
damaged. Try installing the module into another slot.
00 0003 Conguration of module
failed.
00 0004 Conguration of module
failed.