EasyManua.ls Logo

ABB ACS880-01-061A-3+N5350 - Page 190

ABB ACS880-01-061A-3+N5350
247 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting 13-173AXD50000011888
Table 13-2 Fault Messages (Alphabetical by Keypad Text)
Fault Fault # Cause What to do
DDCS controller
comm loss
Programmable fault: 60.59
DDCS controller comm
loss function
7581 DDCS (ber optic)
communication between
drive and external
controller is lost.
Check status of controller. See user documentation of
controller.
Check settings of parameter group 60 DDCS
communication.
Check cable connections. If necessary, replace cables.
MF comm loss
Programmable fault: 60.09
M/F comm loss function
7582 Master/follower
communication is lost.
Check status of other drives on the master/follower link.
Check settings of parameter group 60 DDCS
communication.
Check cable connections. If necessary, replace cables.
Line side unit
faulted
7583 The supply unit (or other
converter) connected
to the inverter unit has
generated a fault.
Check fault status of supply unit (or other converter).
Refer to the rmware manual of the supply unit.
AI supervision
Programmable fault:
12.03 AI supervision
function
80A0 An analog signal is
outside the limits specied
for the analog input.
Check signal level at the analog input.
Check the wiring connected to the input.
Check the minimum and maximum limits of the input in
parameter group 12 Standard AI.
Signal supervision
(Editable message text)
Programmable fault:
32.06 Supervision 1 action
32.16 Supervision 2 action
32.26 Supervision 3 action
80B0 Fault generated by
a signal supervision
function.
Check the source of the fault (parameter 32.07, 32.17 or
32.28).
External fault 1
(Editable message text)
Programmable fault: 31.01
External event 1 source
31.02 External event 1 type
9081 Fault in external device 1. Check the external device.
Check setting of parameter 31.01 External event 1 source.
External fault 2
(Editable message text)
Programmable fault: 31.03
External event 2 source
31.04 External event 2 type
9082 Fault in external device 2. Check the external device.
Check setting of parameter 31.03 External event 2 source.
External fault 3
(Editable message text)
Programmable fault: 31.05
External event 3 source
31.06 External event 3 type
9083 Fault in external device 3. Check the external device.
Check setting of parameter 31.05 External event 3 source.
External fault 4
(Editable message text)
Programmable fault: 31.07
External event 4 source
31.08 External event 4 type
9084 Fault in external device 4. Check the external device.
Check setting of parameter 31.07 External event 4 source.
External fault 5
(Editable message text)
Programmable fault: 31.09
External event 5 source
31.10 External event 5 type
9085 Fault in external device 5. Check the external device.
Check setting of parameter 31.09 External event 5 source.
Safe torque off 1 FA81 Safe torque off function is
active, ie. STO circuit 1 is
broken.
Check safety circuit connections. For more information,
see appropriate drive hardware manual and description of
parameter 31.22 STO indication run/stop.
Safe torque off 2 FA82 Safe torque off function is
active, ie. STO circuit 2 is
broken.