3AXD50000011888F-2 ModbusRTU Setup
Group 58: Embedded Fieldbus
58.01 Protocol Enable = ModbusRTU
58.03 Node Address = 1 This is the drive’s node address on the Modbus RTU network
58.25 Control Prole = Transparent
58.26 EFB Ref1 Type = Speed Speed scaling is 1 unit = 1 rpm
58.30 EFB status word transparent = 6.11[16] Status Word
58.31 EFB act1 transparent source = 1.1[16] Actual Speed
58.34 Word order = HI-LO
58.110 Data I/O 10 = 1.7[16] Motor Current
58.111 Data I/O 11 = 1.11[16] DC Bus Voltage
58.112 Data I/O 12 = 1.14[16] Motor Power
Last step is to restart the fieldbus interface so the above settings take effect:
Do this any time you make a change to Group 58 parameters!
58.06 Communication Control = Refresh settings
That should complete the eldbus setup on the drive.
If this were a startup in the eld, next step would be to explain the control word and status word structure and reference/
actual value scaling to the PLC technician. The rest of this document is devoted to understanding how that works.
Simulating a ModbusRTU Master:
PLC INPUT DATA