3AXD50000011888 ModbusRTU Setup F-3
We rst need to connect our laptop to the drive’s D2D port (connector “XD2D” to be specic). Most of us will use a USB to
RS-232 serial converter. That will be connected to an RS-232 to RS-485 converter. And that will connect to the drive’s D2D
port.
USB to RS-485 serial converters are also available.
Pay attention to RS-485 signal polarity. Generally “A” is (-) and “B” is (+). If communication just doesn’t work, try swapping
these lines. It’s also a good practice to terminate the drive end of the bus by turning ON switch J3 (push the red slider to the
right).
Once the hardware is setup, we will use a software program called ModbusPoll. Some familiarity with this software is
assumed. You can simply open the three ModbusPoll setup les that should accompany this guide, or you can set them up
from scratch:
Figure F-2
PLC OUTPUT DATA
PLC INPUT DATA