EasyManua.ls Logo

ABB COMMANDER 150 - Page 17

ABB COMMANDER 150
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
8
300.3
A3.hP
•1
t-StOP
123456
rSt-n
t-GO
SEC.tOt
•3
•3
•4
34.6
A3 HYS
•2
3 SET UP MODE…
…3.2 Setup Level (Level 2)
•1 Not displayed if the alarm is disabled (None selected) – see section 4.3.2
•2 Only displayed if custom alarm hysteresis is selected – see section 4.3.2
•3 Only displayed if enabled in the Configuration Level – see section 4.3.3
•4 A digital input can also be used to reset the batch total.
Alarm 3 Trip Point
Alarm type
[In engineering units]
Alarm 3 Hysteresis Value
[In engineering units]
Totalizer Value
rSt-Y reset
rSt-n do not reset
To reset the maximum value, select
rSt-Y then press
the
key.
Totalizer Stop/Go
t-GO start totalizer
t-StOP stop totalizer
Setting to
t-GO starts the totalizer counting towards
the predetermined value. Setting to
t-StOP holds the
totalizer at its present value.
Continued on next page