Configuring CoreSense M10 69
Activating the thermal pump
NOTICE
The thermal pump is designed to operate while immersed in transformer oil. It will fail
within minutes if operated in air.
For configuration purposes, the sensor head can be powered when it does not contain any oil. However,
the thermal pump must be turned OFF.
The CoreSense M10 sensor head is delivered with the thermal pump turned OFF. When installation is
complete and the sensor head is in contact with oil, make sure to activate the thermal pump.
To activate the thermal pump:
1 From the CoreSense M10 dashboard (see Figure 47), click Settings. The Settings page appears (see
page 67.
2 Click Administration settings and enter your password (for more information on setting passwords,
see Figure 51 on page 67).
3 Scroll down to the Application settings section and check the Enable thermal pump box.
4 At the bottom of the page, click Apply to confirm activation of the thermal pump.
Figure 54 Enabling the thermal pump