ACH550-UH User’s Manual 55
Start-Up
0131 PID 2 FBK - - -
The
PID 2 controller feedback signal.
• Units and scale defined by PID parameters 4206 & 4207.
0132 PID 1 DEVIATION - - -
The difference between the
PID 1 controller reference value and actual value.
• Units and scale defined by PID parameters 4006/4106 & 4007/4107.
0133 PID 2 DEVIATION - - -
The difference between the
PID 2 controller reference value and actual value.
• Units and scale defined by PID parameters 4206 & 4207.
0134 COMM RO WORD 0…65535 1 0
Free data location that can be written from serial link.
• Used for relay output control.
• See parameter 1401.
0135 COMM VALUE 1 -32768…+32767 1 0
Free data location that can be written from serial link.
0136 COMM VALUE 2 -32768…+32767 1 0
Free data location that can be written from serial link.
0137 PROCESS VAR 1 - 1
Process variable 1
• Defined by parameters in Group 34: Panel Display / Process Variables.
0138 PROCESS VAR 2 - 1
Process variable 2
• Defined by parameters in Group 34: Panel Display / Process Variables.
0139 PROCESS VAR 3 - 1
Process variable 3
• Defined by parameters in Group 34: Panel Display / Process Variables.
0140 RUN TIME 0…499.99 kh 0.01 kh 0 kh
The drive’s accumulated running time in thousands of hours (kh).
0141 MWH COUNTER 0…9999 MWh 1 MWh -
The drive’s accumulated power consumption in megawatt hours. Can not be reset.
0142 REVOLUTION CNTR 0…9999 1 0
The motor’s accumulated revolutions in millions of revolutions.
0143 DRIVE ON TIME (HI) 0…65535 days 1 day 0
The drive’s accumulated power on time in days.
0144 DRIVE ON TIME (LO) 0…43200hh:mm:ss 2 s 0
The drive’s accumulated power on time in 2 second ticks (30 ticks = 60 seconds).
0145 MOTOR TEMP -10...200 °C/ 1 0
0...5000 Ohm /
0…1
Motor temperature in degrees centigrade / PTC resistance in Ohms.
• Applies only if motor temperature sensor is set up. See parameter 3501.
Group 01: Operating Data
Code Description Range Resolution Default S