10-8 Parameter Denitions MN448
Parameters in the Long parameter mode
No. Name/Value Description Default
1302 ANALOG IN 1 SCALING
Scales the analog input by this factor, (as a % of the full scale range of this
input).
100.0
0.0…2000.0 % Example: If parameter 1300 ANALOG INPUT 1 FORMAT is set for 0 – 10V,
and the scaling factor is set to 200.0%, a 5 Volt input will result in the drive
running at maximum speed as set in parameter 2008 MAX SPEED LIMIT
1304
ANALOG IN 2 FORMAT Selects the type of reference source into terminal 4.
U 0-0
U 0-0
0 to 10 Volt Signal
A 0-0
0 to 20mA Signal
t 4-0
4 to 20mA Signal, the DRIVE will trip and show the fault code 000 if the
signal level falls below 3mA
r 4-0
4 to 20mA Signal, the DRIVE will ramp to stop if the signal level falls below
3mA
t 0-4
20 to 4mA Signal, the DRIVE will trip and show the fault code 000 if the
signal level falls below 3mA
r 0-4
20 to 4mA Signal, the DRIVE will ramp to stop if the signal level falls below
3mA
Ptc-th
Use for motor thermistor