EasyManua.ls Logo

ABB EC Titanium Series - Page 96

ABB EC Titanium Series
103 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus-RTU Example Connection A-9MN448
Register 163: Display Scaling
The parameter value is stored as a combined 16 bit word which is constructed as follows:
High byte Low byte
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Display Scaling Source Display Scaling Factor : 3dp, e.g. 0 – 16000 = 0.000 – 16.000
0 : Motor Speed
1 : Motor Current
2 : Analog Input 2 Signal
3 : PI Feedback
A.10 Modbus Exception Response Telegrams
Under some circumstances, the drive may reply with an Exception Response (error) in response to a request telegram sent
from the network master, for example where the master tries to read a register which does not exist. Exception Responses
which can be generated by the drive are listed below:
Exception Code 1: Invalid Request
Exception Code 2: Invalid Modbus register
Exception Code 3: Register Value Out of Range
Exception Code 6: Drive Busy
Exception codes may be returned under the following conditions:
Network Master sends an unsupported Modbus command (e.g. Read Coils).
Run command issued to drive whilst the drive is not set for Modbus Control Mode (e.g. 1103 <>4).
Run command issued to drives whilst the drive is not enabled (e.g. Digital Input 1 is open).
Run command issued to drive whilst the drive is in a tripped condition.
Network Master attempts to read or write a register that does not exist within the drive.
Network Master attempts to write a holding register with a value outside the range of the register
Drive busy due to internal data transfer. The Network Master should re-send the message after a delay
A.11 Dataflow Example
Read data from register 6
Request: [01] [03] [00] [05] [00] [01] [94] [0B]
(Drive Addr) (Command) (Reg start addr) (No. of Registers) (Checksum)
Reply: [01] [03] [02] [00] [00] [B8] [44]
(Drive Addr) (Command) (No of data bytes) (Data) (Checksum)
Note: The actual start address of register 6 is 5. All data in [ ] is in 8bits Hex format.
Write start command to the register 1 (suppose 1103 = 3, 9902 =0 and digital input 1 is closed):
Request: [01] [06] [00] [00] [00] [01] [48] [0A]
(Drive Addr) (Command) (Reg addr) (Data value) (Checksum)
Reply: [01] [06] [00] [00] [00] [01] [48] [0A]
(Drive Addr) (Command) (Reg addr) (Data value) (Checksum)
Note: The actual address of register 1 on the data link is 0. All data in [ ] is in 8bits Hex format.
Reply can be error message depending on drive parameter settings and digital input status.

Table of Contents

Related product manuals