EasyManua.ls Logo

ABB INSITE PRO M COMPACT SCU100 - SCU100 Dimensions and Technical Data

ABB INSITE PRO M COMPACT SCU100
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.Technical characteristics / specifications
4.1.Overall dimensions and technical data sub-distribution control unit
87
162 64,2
IEC61010-1
Supply voltage [VAC] 90-240 (L1-N)
Voltage measurement range [VAC] 90-240 (L1-N, L2-N, L3-N)
UL 508 / CSA C22.2 No. 14
Supply voltage [VAC] 80-277 (L1-N)
Voltage measurement range [VAC] 80-277 (L1-N, L2-N, L3-N)
General
Frequency [Hz] 50 / 60
Power consumption (L1-N) [VA]
5 .. 45
(depending on number of sensors and I/O modules)
Current measurement range
Current transformer
(secondary wire of CT)
[A]
nominal: 5
max.: 6
Data refresh time 1sec / 30 sec (depending on type of data)
Operating temperature [°C] -25 .. +60
Storage temperature [°C] -40 .. +85
LAN (RJ45 connector) [Mbit/s] 100
Modbus RTU [Baud] RS485 2-wire, 2400..115200
Cable cross section*
1.0.. 2.5 mm²
(max. 0.8 Nm)
Stripping length [mm] 10
Tightening torque of screws [Nm] 0.5..0.8
Mounting DIN-rail 35 mm DIN50022
Dimensions [mm] 160.0 x 87.0 x 64.9 (9 DIN modules)
Overvoltage category II
Pollution degree 2
Altitude [m] 2000
Safety class IP20
Main circuit accuracy
Voltage 
Current 
Harmonic component (up to 2500Hz) 
Active power 
Apparent power 
Reactive power 
Power factor 
Standards
Electrical safety IEC 61010-1
EMC IEC 61326-1
*Line protection is recommended (acc. IEC61439) min. 6A, max 8A for 1mm2, 12A for 1.5mm2, 20A for 2.5mm2.
Do not operate the equipment outside the specified technical data and not intended use.
16 SCU100 INSITE PRO M COMPACT USER MANUAL

Related product manuals