4.2.Overall dimensions and technical data I/O modules
87
35,865
Input module
DM11
Output module
DM00
Input and Output
module
DM10
Number of digital channels 4 Input 4 Output 2 Input + 2 Output
Voltage*
active input:
22-26 VDC
relay output:
5VDC-240 VAC
active input:
22-26 VDC
relay output:
5VDC-240 VAC
Current*
active input:
4mA
relay output:
5mA-2.5A
Max 4.5A (<5sec)
active input:
4mA
Relay output:
5mA-2.5A
Max 4.5A (<5sec)
Pulse minimum duration** [ms]
5 n/a 5
Pulse frequency** [Hz]
100 n/a 100
Screwless terminals cross
section [mm
2
]
0,08...2,5 0,08...2,5 0,08...2,5
Using ferrules [mm
2
]
0,25...1,5 0,25...1,5 0,25...1,5
Stripping length [mm] 5 ... 6 5 ... 6 5 ... 6
Operating temperature [°C]
-25…+60
Bearing temperature [°C]
-40…+85
Mounting method
35 mm DIN rail (DIN 50022) or SMISSLINE TP plug base
Dimensions [mm]
36x88x65 36x88x65 36x88x65
Overvoltage category
II acc. to
(IEC61010-1)
Pollution degree
2
Altitude
m 2000
Safety class
IP20
IK code
IK06(1J)
Standards compliance
IEC 61010
EMC
IEC 61326-1
*relay output values reported are applicable to resistive load
**applicable only to active inputs
Every active input is protect by 400V silicon diodes with fuse resistor against misunderstanding in
connections like connecting 230Vac mains instead relays/transistor output of meter.
There is one fuse per 2 active input channels.
Do not operate the equipment outside the specified technical data and not intended use.
SCU100 INSITE PRO M COMPACT USER MANUAL 17