10.5.Automation
This page allows to set automatic actions on selected devices if a specific configured event occurs.
The automatic action can be set only for I/O Modules which have output channels already configured in
“Configuration – Devices – I/O Modules”
When adding or editing an automation, please set the following:
IF
Name Set the name of the automation
Category Select the type of the device
Device
Select the devices already defined in “Configuration –
Devices” according to the Category selected
Alert Type
Type of alarm: “Cross-up”, “Cross-down”. “Status change”
only in case of I/O Modules devices
Measure
Set the specific measure to monitor according to the
device selected
Threshold Threshold of selected measure
Time delay
Define for how long the event criteria should be fulfilled
in order to consider the occurrence as an event
Send alarm
If the box is selected, then alarm will be shown in alarms
log.
THEN
Device
Select the I/O Module with output channels already
defined in “Configuration – Devices”
Channel
Select the output channel of the I/O Module already
selected
Action
Set the action (open/close) to be performed by the
channel if the condition previously configured occurs
SCU100 INSITE PRO M COMPACT USER MANUAL 45