108  FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D   
 
 
… 8  Operation 
Filling function 
 
 
1 Supply tank 
2 Sensor 
3  Start / stop fill operation  
(digital input through plug-in 
card) 
4 Fill valve 
5 Filling tank 
VO Valve open  
(filling started) 
VC Valve closed 
(fill quantity reached) 
t
1  Valve closing time 
t
2 Overrun time 
Figure 76:  FillMass fill function 
 
 
The optional filling function allows filling with filling times> 3 
seconds. 
 
Filling quantity is configurable and the filling process can be 
started via the digital input (plug-in card). 
As soon as the filling quantity has been reached, the valve can be 
closed via the digital output. 
Filling quantity correction is calculated by measuring the overrun 
quantity. 
Additionally, the low flow cut-off can be configured if required. 
 
 
 
 
 
Setup 
For the configuration of the fill function, the following steps 
must be performed: 
1.  The fill function must be active. See also the ‘Device Setup 
/ ...Transmitter / ...Feature Settings / ...’ menu. 
2.  One digital output must be configured as a binary output 
with the function ‘Batch End Contact’. See also the 
‘Input/Output / ...’ menu. As an option, one digital input 
(option module) can be configured with the function 
‘Start/Stop Batching’ at the start of the filling process. 
3.  The parameters for the fill function must be configured. 
See also the ‘Totalizer / ...Batching / ...’ menu. 
 
Note 
During fast filling processes, the damping should be set to the 
minimum value to guarantee the greatest possible accuracy of 
the fill quantity. 
See also the ‘Device Setup / ...Transmitter / ...’ menu. 
 
 
Brief overview of configurations 
 
Configuration of digital output 41 / 42 as pulse output for 
forward flow and digital output 51 / 52 as pulse output for 
reverse flow. 
 
Menu / parameter  Parameter setting
Input/Output / Dig.Out 41/42 / … 
Mode  ⇒ Pulse
Outp. Flow Direction  ⇒ Forward
Input/Output / ...Setup Pulse Output 
Output Value Pulse  ⇒ Pulse Volume Flow
Pulses per Unit  ⇒  Setting in accordance with
requirement
Pulse Width  ⇒  Setting in accordance with
requirement
Input/Output / Dig.Out 51/52 
Mode  ⇒ Follow DO 41/42