30  FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D   
 
 
… 6  Electrical connections 
… Sensor grounding 
 
Metal pipe with fixed flanges 
 
 
G12021
1
1
AB
 
A Flange design 
B  Wafer type design 
1 Ground terminal 
Figure 34:  Metal pipe, without liner (example) 
 
Use a copper wire [at least 2.5 mm
2
 (14 AWG)] to establish the 
connection between the ground terminal of the sensor, the 
pipeline flanges and a suited grounding point in accordance with 
the figure. 
 
 
Metal pipe with loose flanges 
 
 
G12022
1
1
2
2
AB
 
A Flange design 
B  Wafer type design 
1  Threaded bolts M6   
2 Ground terminal 
Figure 35:  Metal pipe, without liner (example) 
 
1. Solder the threaded bolts M6 to the piping and connect the 
ground in accordance with the figure. 
2. Use a copper wire [at least 2.5 mm
2
 (14 AWG)] to establish 
the connection between the ground terminal of the sensor 
and a suited grounding point in accordance with the figure. 
 
 
 
 
 
 
Plastic pipes, non-metallic pipes or pipes with insulating 
liner 
 
 
G12023
2
1
1
3
AB
3
2
 
A Flange design 
B  Wafer type design 
1  Ground terminal  
2 Terminal lug 
3 Grounding plate 
Figure 36:  Plastic pipes, non-metallic pipes or pipes with insulating liner 
 
For plastic pipes or pipes with insulating lining, the grounding of 
the measuring medium is provided by the grounding plate as 
shown in the figure below or via grounding electrodes that must 
be installed in the device (option). 
If grounding electrodes are used, the grounding plate is not 
necessary. 
 
1. Install the sensor with grounding plate in the piping. 
2. Connect the terminal lug of the grounding plate and ground 
connection on the sensor using the grounding strap. 
3. Use a copper wire with at least 2.5 mm
2
 (14 AWG)) to 
establish a connection between the ground connection and a 
suited grounding point.