FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D  95 
 
Menu: Communication  
 
Menu / parameter  Description 
Communication 
...HART  Selection of submenu ‘...HART’ using  . 
...Modbus  Selection of submenu ‘...Modbus’ using  . 
...Profibus  Selection of submenu ‘...Profibus’ using  . 
 
Communication / ...HART 
Device Address  Selection of HART device address. 
Note 
The HART protocol has provisions for creating a bus with up to 15 devices (1 to 15)). 
If an address greater than 0 is set, the device operates in multidrop mode. The current output 31 / 32 / Uco is fixed to 4 mA. 
HART communication takes place only through current output 31 / 32 / Uco. 
Loop Current Mode  Selection of the operating mode for current output with HART communication. 
• Multidrop Fixed 
• Normal Signaling 
HART Tag  Entry of a HART TAG number as unique identifier for the device.  
Alphanumeric, a maximum of 8 characters, upper case only, no special characters. 
HART Long Tag  Entry of a HART TAG number as unique identifier for the device. 
Alphanumeric, maximum of 32 characters, ASCII 
Only starting from HART version 7! 
HART Descriptor  Entry of a HART descriptor. 
Alphanumeric, a maximum of 16 characters, upper case only, no special characters. 
HART Message  Display of the alphanumeric TAG number. 
HART Manuf. ID  Display of the HART manufacturer ID. ABB = 26 
HART Device ID  Display of the HART device ID. 
HART Find  Select whether the transmitter must respond to the HART command 73 (Find Device). 
•  Off: The transmitter does not respond to command 73. 
•  Once: The transmitter responds once to command 73. 
•  Continuous: The transmitter always responds to command 73. 
Last HART Command  Display of the most recently sent HART command.