96  FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D   
… 8  Operation 
… Parameter descriptions 
 
Menu / parameter  Description 
Communication / ...Modbus 
Address  Setting the Modbus device address (1 to 127). 
IEEE Format  Selection of the byte order for the Modbus communication. 
•  Enabled: If the IEEE format is activated, the data words are sent in the ‘little endian’ format with the lowest value word 
first. 
•  Disabled: If the IEEE format is deactivated, the data words are sent in the standard Modbus ‘bigendian’ format. 
Factory setting: Enabled. 
Baud Rate  Selection of the transmission speed (baud rate) for the Modbus communication. 
Factory setting: 9600 baud. 
Parity  Selection of the parity for the Modbus communication. 
Factory setting: Odd. 
Stop Bits  Selection of the stop bits for the Modbus communication. 
Factory setting: One stop bit 
Response Delay  Setting of the pause time in milliseconds after receiving a Modbus command. The device sends a response no earlier than 
expiration of the set pause time. 
Factory setting: 10 ms 
 
Communication / ...Profibus 
Address  Set the PROFIBUS DP® device address (1 to 126). 
Ident Nr. Selector  Display the PROFIBUS DP® identification number 
• 9700: 1xAI 
•  9740: 1xAI + 1xTOT 
• 3432: ABB-specific 
Comm State  Display the PROFIBUS communication status. 
•  Offline: No PROFIBUS® communication. 
•  Stop: Bus active, device not active. 
•  Clear: Device is being initialized. 
•  Operate: Cyclic communication is active. 
Baud Rate  Display the transmission speed (baud rate) for the PROFIBUS® communication. 
The baud rate is automatically detected and does not need to be configured manually. 
PB Manufacturer ID  Display the PROFIBUS DP® manufacturer ID 
• 26: ABB