… 7  Commissioning 
Checks prior to commissioning 
 
The following points must be checked before commissioning the 
device: 
•  Correct wiring in accordance with Electrical connections 
on page 29. 
•  Correct grounding of the sensor. 
•  The ambient conditions must meet the requirements set 
out in the specification. 
•  The power supply must meet the requirements set out on 
the name plate. 
 
 
Parameterization of the device 
 
The FEP630, FEH630 can be commissioned and operated via the 
integrated LCD indicator (option, see Parameterization via the 
menu function Easy Setup on page 56). 
 
Alternatively, the FEP630, FEH630 can also be commissioned and 
operated via ABB Asset Vision Basic (FEP6xx DTM). 
 
 
Parameterization with the optional LCD indicator 
 
1 Local operating interface 
2  Coupler connectors for LCD 
indicator 
3 LCD indicator 
Figure 70:  Optional LCD indicator 
 
For devices without LCD indicator, an optional LCD indicator for 
parameterization can be connected. 
 
 
 
 
 
Parameterization via the local operating interface 
 
 DANGER 
Explosion hazard 
Risk of explosion during operation of the device with open 
terminal box! 
•  Only perform parameterization of the device via the local 
operating interface outside potentially explosive 
atmospheres! 
 
A PC / Notebook and the USB interface cable are needed to 
configure the device via the device local operating interface. 
By combining the HART-DTM and the softwareflow available at 
www.abb.com/ABB AssetVision, all parameters can also be set 
without a fieldbus connection. 
 
G12157
 
1 Local operating interface 
2 USB-interface cable 
3  PC / Notebook 
Figure 71:  Connection to the local operating interface 
 
1.  Open device terminal box. 
2.  Connect programming plug to the local operating interface 
of the device. 
3.  Insert USB interface cable into a free USB female connector 
on the PC / notebook. 
4.  Switch on the device power supply. 
5.  Start ABB AssetVision and perform the parameterization of 
the equipment. 
 
Detailed information on operating the software is available in 
the relevant operating instructions and the DTM online help.