FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D  79 
 
 
 
Menu: Easy Setup 
 
Menu / parameter  Description 
Easy Setup 
Language  Selection of the menu language (German, English, French, Spanish, Italian, Chinese, Portuguese). 
Unit Volumeflow Qv  Selection of the unit for the volume flow (for example for the parameters Qv
Max
 / Qv
Max
DN and for the corresponding 
process value). 
Default setting: l/min 
Table 1: Units for the volume flow on page 78 
Qv Max 1  Setting the upper range value 1 (Measuring range = 0 to Qv Max 1) for the volume flow for forward flow and reverse flow . 
Default setting: 1 × Q
max
DN 
Unit Vol. Totalizer  Selection of the unit for the volume totalizers and the pulse outputs. 
Default: l (liter) 
Table 4: Units for the volume totalizer on page 78 
Dig.Out 41/42 Mode  Selection of the operating mode for the digital output 41 / 42. 
•  Off: Digital output 41 / 42 deactivated. 
•  Logic: Digital output 41 / 42 as a binary output (e.g. as an alarm output). 
•  Pulse: Digital output 41 / 42 as a pulse output. In pulse mode, pulses are output per unit (e.g. 1 pulse per m
3
). 
•  Frequency: Digital output 41 / 42 as a frequency output. In frequency mode, a frequency is issued that is proportional to 
the flow rate. The maximum frequency can be configured in accordance with the upper range value. 
Default setting: Pulse 
Pulses per Unit 
 
Set pulses per volume or per mass flow unit, and the pulse width for the digital output operating mode ‘Pulse’. The pulse 
value and pulse width are interdependent and calculated dynamically (pulses per unit: 1 to 10000 / s, pulse width: 
0.1 to 2000 mS). 
Only available if a digital output has been configured as a pulse output, and the volume flow or mass flow has been selected 
as the process variable to be output. 
Pulse Width 
Upper Frequency  Sets the upper range value frequency for the digital output operating mode ‘Frequency’. The entered value (0 to 10500 Hz) 
corresponds to 100 % flow. 
Only available if a digital output has been configured as a frequency output, and the volume flow or mass flow has been 
selected as the process variable to be output. 
Damping  Select the damping. 
The value set here (0.02 to 60 s) refers to 1 τ (Tau). The value refers to the response time for a step flowrate change. It 
affects the instantaneous value in the display and at the current output. 
Default setting: 1 second 
Curr.Out at Alarm  Selection of status of the current output in error condition. 
The output ‘Low Alarm’ or ‘High Alarm’ current is set in the subsequent menu. 
Low Alarm  Setting the current (3.5 to 3.6 mA) for low alarm. 
High Alarm  Setting the current (21 to 22.6 mA) with high alarm. 
System Zero  Starts the automatic zero point balancing using  . Automatic zero point balancing takes approx. 60 seconds. 
Note 
Prior to starting the zero point adjustment, make sure that: 
•  There is no flow through the sensor (close all valves, shut-off devices etc.) 
•  The sensor must be filled completely with measuring medium for measurement.