FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D  115 
 
Error no. / Range  Error text  Current output  Digital output  Pulse output  LCD display  Error maskable? 
F090.035 / 
Electronics 
ADC RX210 com. error. 
Call service. 
    0 Hz  0 %  No 
F088.012 / 
electronics 
FEB communication error. 
EMC disturbance. Call Service. 
0 Hz  0 %  No 
F086.018 / 
Electronics 
Curr.Out 31 / 32 com error. 
Defective Board. EMC 
disturbance. Call Service. 
Current value - no 
change. 
Current value - no 
change. 
No 
F084.010 / 
electronics 
NV data defect. 
Data storage irreparable. Call 
Service. 
0 Hz  0 %  No 
F082.013 / 
Electronics 
Incompatible Frontend Board. 
Frontend not fit to 
Motherboard. Call Service. 
0 Hz  0 %  No 
F081.025 / 
electronics 
MB voltages outside range. 
Defective Motherboard HW. 
Call Service. 
0 Hz  0 %  No 
C078.003 / Config.  Flowrate to zero. 
Check digital in terminals. 
4 mA (0 % flow)  Current value - no 
change. 
0 Hz  0 %  Menu ‘...Group 
Masking’. 
C076.005 / Config.  All totalizer stopp. 
Check digital in terminals. 
Current value - no 
change. 
Current value - no 
change. 
Current value - no 
change. 
Current value - no 
change. 
C074.006 / Config.  Totalizer reset. 
Reset of one or more 
Totalizers. 
Current value - no 
change. 
Current value - no 
change. 
Current value - no 
change. 
Current value - no 
change. 
Menu ‘...Group 
Masking’. 
C072.002 / Config.  Simulation is on. 
Simulated values. 
Switch off Simulation Mode. 
Current value - no 
change. 
Current value - no 
change. 
Current value - no 
change. 
Current value - no 
change. 
 
C070.026 / Config.  An alarm is  simulated. 
Switch off alarm simulation. 
Current value - no 
change. 
Current value - no 
change. 
Current value - no 
change. 
Current value - no 
change.