32  FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D   
 
… 6  Electrical connections 
… Sensor grounding 
 
 
Internally insulated piping with cathodic corrosion 
potential 
G11050
3
1066
1
2 45
8 7 6
9
23
 
1 Piping flange 
2 Insulating plate 
3  Gasket / insulating ring 
4 Grounding plate 
5  Insulating pipe   
6 Flange 
7 Liner 
8 Insulation 
9 Sensor 
Figure 38:  View Screw bolts 
 
Install grounding plates on each side of the flowmeter sensor. 
Insulate the grounding plates from the pipe flanges and connect 
them to the flowmeter sensor and to functional ground.  
The screw bolts for flange connections should be mounted with 
insulation. The insulation plates and the insulation pipe are not 
included in the delivery. They must be provided onsite by the 
customer. 
 
 
G11049
11
2
A
B
3
B
B
B
 
A Connection line corrosion 
potential* 
B  Insulated screw bolts without 
grounding plates 
1  Insulated piping   
2 Functional ground 
3 Grounding plates 
*  ≥ 4 mm
2
 Cu, not included in the delivery, to be provided on-site 
Figure 39:  sensor with grounding plate and functional ground 
 
The corrosion protection potential must be diverted through a 
connecting line 
A away from the insulated installed sensor.