FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D  93 
 
Menu / parameter  Description 
Input/Output / ...Dig.Out V1/V2 / ...Setup Logic Output 
Input/Output / ...Dig. Out V3/V4 / ...Setup Logic Output 
Logic Output Action  Selection of binary output function. 
See description ‘„Input/Output / ...Dig.Out 41/42 / ...Setup Logic Output’. 
Active Mode  Select switching properties for the binary output. 
•  Active High: Normally open 
•  Active Low: Normally closed 
Default setting: Active High. 
 
Input/Output / ...Dig.Out V1/V2 / ...Alarm Config 
Input/Output / ...Dig. Out V3/V4 / ...Alarm Config 
General Alarm  Select error messages signaled via the binary output V1 / V2 or V3 / V4. 
Only if the parameter ‘Logic Output Action’ is set to Alarm Signal. 
Qv Volumeflow Max 
Qv Volumeflow Min 
EPD 
TFE 
Gas Bubble 
Conductivity 
Sensor Temperature 
In house Temp 
 
Input/Output / ...Dig.In V1/V2 
Input/Output / ...Dig.In V3/V4 
Function  Select a function for the digital input. 
•  No function: No function. 
•  Reset all Totalizer: Counter reset for all counters (forward flow, reverse flow and difference totalizer) 
• Stop all Totalizer: External counter stop for all counters (forward flow, reverse flow and difference totalizer) 
•  Auto. Zero Adjust: Start external zero point balancing. 
•  Set Flowrate to zero: Sets flow measurement to 0. 
•  Start/Stop Batching: Start / stop fill operation (only when FillMass function is activated). 
•  Dual Range Mass: Switchover Qm Max 1 / Qm Max 2. 
•  Dual Range Volume: Switchover Qv Max 1 / Qv Max 2. 
Active Mode  Select switching properties for the digital input. 
Delay Time  Selection of delay time for suppressing EMC faults on the digital input.