The PHASORREPORT filtering window is designed to receive updated input every 0.9
ms and therefore the application will fail.
Rule 2:
The same SMAI or 3PHSUM block can be connected to more than one
PHASORREPORT block only if all the connected PHASORREPOR
T blocks have
similar instance number or only if all the connected PHASORREPORT blocks have
similar settings for SvcClass and ReportRate. Figure
45 shows the settings for
PMUREPORT function block demonstrated by PCM600 Parameter Setting T
ool
(PST).
IEC140000126-2-en.vsd
IEC140000126 V2 EN-US
Figure 45: PMUREPORT settings in PCM600 PST
Figure
46 shows an example of correct connection of SMAI and PHASORREPORT
blocks in ACT where two dif
ferent SMAI blocks are connected to different
PHASORREPORT blocks with different instance numbers. In this example, as the
PHASORREPORT blocks have different instance numbers and different settings for
SvcClass and ReportRate, a separate SMAI block is used for each PHASORREPORT
block.
Section 6 1MRK 502 071-UUS A
Wide area measurement system
122 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062