EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - Page 130

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IEC140000128-2-en.vsd
IEC140000128 V2 EN-US
Figure 47: An example of wrong connection of SMAI and PHASORREPORT
blocks in ACT
Rule 3:
This rule is only related to the connection of 3PHSUM block to the PHASORREPORT
block. If 3PHSUM block is configured to use external DFT reference (from SMAI
reference block), it shall only be connected to the same PHASORREPORT block
instance as the one the SMAI reference block is connected to. In other words, both the
SMAI reference block and 3PHSUM block (3PHSUM block with external DFT
reference) shall be connected to the same instance of PHASORREPORT block
(PHASOR1-32 of Instance number 1 or 2).
Figure
48 shows an example of correct connection of 3PHSUM and
PHASORREPORT blocks in ACT where SMAI3 is configured as the reference block
for DFT reference external out (DFTRefExtOut) and 3PHSUM uses external DFT
reference (from SMAI3). Figures 49 and 50 show the corresponding setting
parameters.
Section 6 1MRK 502 071-UUS A
Wide area measurement system
124 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual

Table of Contents

Related product manuals