IEC140000131-1-en
IEC140000131 V1 EN-US
Figure 50: 3PHSUM setting parameters example-showing that 3PHSUM is using
the External DFT reference coming indirectly from SMAI3
Figure
51 shows an example of wrong connection of 3PHSUM and PHASORREPORT
blocks in ACT where SMAI3 is configured as the reference block for DFT reference
external out (DFTRefExtOut) and 3PHSUM uses external DFT reference (from
SMAI3).
IEC140000132-2-en.vsd
IEC140000132 V2 EN-US
Figure 51: An example of wrong connection of 3PHSUM and PHASORREPORT
blocks in ACT
If settings for PMUREPORT instances (PHASORREPORT1 instances 1 and 2 above)
differ for SvcClass or ReportRate, then the synchrophasor reported by PHASOR2
connection from PHASORREPORT1 instance 2 will not be compliant with IEEE
C37.118 standard. The reason is as in the rule 2, the filtering in SMAI/3PHSUM block
Section 6 1MRK 502 071-UUS A
Wide area measurement system
126 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual